29209-0-0911 Page 13
VerticalThroughtheRoofApplications
The Gas Fireplace Insert has been approved for:
a) Vertical installations up to 35 feet in height (top of insert to
cap).
b) Two sets of 45 degree elbow offsets (bends in exvent) within
the vertical installation. From 0 to a maximum of 8 ft. of vent
pipe can be used between elbows.
c) Wall straps must be used to support offset pipe every 4'.
This application will require that you rst determine the roof pitch
and use the appropriate venting components.
GeneralMaintenance
Conduct an inspection of the venting system semi-annually.
Recommended areas to inspect are as follows:
1. Check areas of the venting system which are exposed to the
elements for corrosion. These will appear as rust spots or
streaks and, in extreme cases, holes. These components should
immediately be replaced.
2. Remove the cap and shine a ashlight down the vent. Remove
any bird nests or other foreign material.
3. Check for evidence of excessive condensate, such as water
droplets forming in the ex venting and subsequently dripping
out at joints or seams. Condensate can cause corrosion of caps,
pipe and ttings. It may be caused by having excessive lateral
runs, or having exterior portions of the system exposed to cold
weather.
4. Inspect joints to verify that no pipe sections or ttings have been
disturbed and, consequently, loosened. Also, check mechanical
supports, such as wall straps or plumbers’ tape for rigidity.
Tall Vent Heights
In some circumstances when venting vertically (20 to 30 feet), it
may require that the ue bafe vent door be opened to improve
performance. It is especially important during initial cold start-ups.
To adjust, rotate the vent door enough to encourage better draft for
improved combustion.
FIREBOX
BAFFLE
FLUE
BAFFLE
VENT
Figure 11
DeterminingMinimumVentHeightAbovetheRoof.
WARNING
MajorU.S.buildingcodesspecifyminimumchimneyand/or
ventheightabovetherooftop.Theseminimumheightsare
necessaryintheinterestofsafety.Thesespecicationsare
summarizedinFigure9.
Figure9
Note that for steep roof pitches, the vent height must be increased.
In high wind conditions, nearby trees, adjoining roof lines, steep
pitched roofs, and other similar factors can result in poor draft, or
down-drafting. In these cases, increasing the vent height may solve
this problem.
When terminating the vent cap near an exterior wall or overhang,
maintain minimum clearances as shown in Figure 10.
ROOF PITCH H (Min.)
Flat to 6/12 12" (305 mm)
6/12 to 7/12 15" (381 mm)
Over 7/12 to 8/12 18" (457 mm)
Over 8/12 to 16/12 24" (610 mm)
Over 16/12 to 21/12 36" (914 mm)
VERTICAL TERMINATION
Figure 10
MIN.
12"
MIN.
24"
24"
MIN.
C
L
Comments to this Manuals